Lessons learned: Preventing high-pressure nitrogen cylinder ruptures

IMCA provides lessons learned from an incident in which, a high pressure Nitrogen cylinder in a quad of 12 cylinders located on a drill rig floor ruptured without warning.

The cylinders were charged to 2,400psi and were not connected to anything else at the time of the incident. The rack was destroyed and the other cylinders in the quad were propelled by the blast up to 15m away.

Why did it happen

The base of the cylinder that ruptured was heavily corroded. Other cylinders in the quad had evidence of similar but less severe corrosion.

The cylinders were 9 years into their 10-year hydrotest cycle, and had been visually inspected by the supplier in accordance with applicable industry guidance, when they were refilled some three months before the incident, before being loaded out to the rig. However, the severe corrosion that caused the rupture was not spotted during this inspection;

The cylinder that ruptured was located in the middle of the quad and therefore not easy to properly inspect without disassembly of the quad.

Calculations showed that the fatal blast zone for a single cylinder of this size pressurised to 2,400psi would be around 1.5 metres. The severity of the blast caused the rack to be destroyed and the other cylinders to be propelled across the deck.